EPD-IES-0035418:001

Carrier AquaEdge® 19MV Water-Cooled Centrifugal Chiller 19MV-73L73L489E39: R-1234ze(E)

The AquaEdge® 19MV Water-Cooled Centrifugal Chiller is a premium solution designed for exceptional efficiency, reliability, and adaptability in large-scale cooling applications. It features Carrier’s advanced EquiDrive™ two-stage back-to-back compressor technology with magnetic bearings, delivering superior performance across a wide operating range, including low-load conditions without the need for hot-gas bypass. This oil-free design minimizes maintenance and maximizes uptime, while the integrated permanent magnet motor and Greenspeed® variable-frequency drive ensure optimal energy savings and quiet operation. The chiller supports multiple low-GWP refrigerants such as R-513A, R-515B and R-1234ze(E), making it environmentally responsible. Its SmartVu™ control panel offers intuitive touchscreen navigation, comprehensive diagnostics, and seamless connectivity with BACnet® and CCN systems. Compact and modular, the 19MV fits through standard double doors, simplifying installation in space-constrained environments. With capacities ranging from 150 to 1,200 tons, it is ideal for commercial buildings, data centers, healthcare facilities, and industrial applications, delivering best-in-class efficiency, reliability, and sustainability. 

The Carrier AquaEdge® 19MV‑73L73L489E39 is a high‑efficiency, water‑cooled centrifugal chiller designed for large commercial and industrial applications, delivering a nominal cooling capacity of 3,517 kW using a two‑stage, back‑to‑back magnetic‑bearing compressor for oil‑free and reliable operation. Operating with the low‑GWP refrigerant R‑1234ze(E), the unit ensures improved environmental performance while maintaining high efficiency, achieving an IPLV of 11.64 W/W. A unit‑mounted VFD enables optimized performance under part‑load conditions.

The system incorporates a 73L two‑pass evaporator with Super B5 copper tubes and a 73L two‑pass condenser with Spike 3 copper tubes, designed for fresh‑water applications. It operates under standard conditions of approximately 12.22°C/6.67°C chilled water and 29.5°C/35°C condenser water, ensuring stable performance. With a refrigerant charge of 818 kg and optimized hydraulic characteristics, the unit supports efficient and reliable cooling. Suitable for large facilities such as commercial buildings, healthcare infrastructure, data centers, and district cooling systems, the 19MV‑73 series offers a balanced combination of sustainability, efficiency, and robust design.

New
Registration numberEPD-IES-0035418:001
StatusValid
Version date2026-11-04
Validity date2031-11-04
PCR2019:14 Construction products (EN 15804+A2) (version 2.0.1)
Standards conformanceISO 14025:2006, EN 15804:2012+A2:2019/AC:2021, ISO 21930:2017
LicenseeEPD-North America
Geographical scopeGlobal